Template

Swedish aerated concrete house (1955–1975)

Single-leaf wall of autoclaved aerated concrete (lättbetong, Siporex/Ytong) with plaster inside and mineral render outside.

  • Sweden
3 layers · 280 mm

Delete “Swedish aerated concrete house (1955–1975)”?

This template will be removed for everyone. This can’t be undone.

Climate

20.0 °C
10 °C 28 °C
38 %
20 % 95 %
-5.0 °C
-30 °C 40 °C
80 %
30 % 100 %

Build-up

Layers from inside to outside

Inside (warm) 3 layers · 280 mm
  1. 1 Interior plaster
    mm
  2. 2 Aerated concrete
    mm
  3. 3 Mineral render (puts)
    mm
Outside (cold)

Result

No condensation

The indoor dew point (5.3 °C) is reached in layer 2 “Aerated concrete” – but so little vapour gets there that the vapour pressure stays below saturation.

U-value
0.50 W/m²K
per EN ISO 6946
Indoor dew point
5.3 °C
20.0 °C · 38 % RH
Inner surface
17.0 °C
46 % RH at the inner surface
sd value
3.1 m
effective layers
Interstitial condensation
at 38 % indoors: outdoor temperature below -8.2 °C
at -5.0 °C outdoors: indoor humidity above 49 %
Surface mould risk
at 38 % indoors: outdoor temperature not down to −30 °C
at -5.0 °C outdoors: indoor humidity above 66 %

Cross-section

Temperature and dew point across the build-up – hover for details

Temperature Dew point (linear vapour pressure) Dew point above temperature Condensation (Glaser) Indoor air dew point
INSIDE20.0 °C · 38 %OUTSIDE-5.0 °C · 80 %12502203-1001020°CwarmcoldDew point 5.3 °C
Values at layer boundaries
Boundaryx [mm]sd [m]θ [°C]θdew [°C]ps [Pa]p [Pa]RH [%]
Inner surface0.00.0017.05.31,94189246
1 | 210.00.2016.94.71,92785544
2 | 3260.02.7-4.3-5.242839592
Outer side280.03.1-4.5-7.641832177

Critical conditions

At which outdoor temperature and indoor humidity does it get critical?

safe Mould risk (surface > 80 %) Interstitial condensation current conditions
020406080100-30-20-1001020% RH insideOutdoor temperature in °C (inside 20.0 °C, outside 80 % RH)

Glaser diagram

Vapour pressure must not touch the saturation pressure

Saturation pressure Vapour pressure (Glaser)
12305001,0001,5002,000Painsideoutsidetotal sd 3.1 m

How it works

Temperature profile

The temperature drops across each layer in proportion to its thermal resistance R = d/λ. Surface resistances are Rsi = 0.25 and Rse = 0.04 m²K/W (0.08 behind a ventilation gap). Layers outside a ventilated air gap are ignored.

Dew point & condensation

The indoor air has a dew point (e.g. 9.3 °C at 20 °C / 50 %). Reaching it inside the build-up alone is not a problem – what matters is how much vapour gets there. The Glaser method compares the vapour pressure with the saturation pressure; where they meet, condensation forms.

Limitations

A steady-state estimate (EN ISO 13788) without capillary transport, moisture storage or thermal bridges. Capillary-active internal insulation is rated conservatively. For a detailed assessment use a hygrothermal simulation (e.g. WUFI).