Template

Modern Swedish house (BBR)

Current timber frame wall (regelvägg) with the vapour barrier protected behind an insulated service layer.

  • Sweden
7 layers · 312 mm

Delete “Modern Swedish house (BBR)”?

This template will be removed for everyone. This can’t be undone.

Climate

20.0 °C
10 °C 28 °C
38 %
20 % 95 %
-5.0 °C
-30 °C 40 °C
80 %
30 % 100 %

Build-up

Layers from inside to outside

Inside (warm) 7 layers · 312 mm
  1. 1 Gypsum plasterboard
    mm
  2. 2 Service layer (mineral wool)
    mm
  3. 3 PE vapour barrier (sd 100 m)
    mm
  4. 4 Mineral wool 035
    mm
  5. 5 Gypsum wind barrier board
    mm
  6. 6 Ventilation gap ventilated
    mm
  7. 7 Wood panel (träpanel) not effective
    mm
Outside (cold)

Result

No condensation

The indoor dew point (5.3 °C) is reached in layer 4 “Mineral wool 035” – but so little vapour gets there that the vapour pressure stays below saturation.

U-value
0.14 W/m²K
per EN ISO 6946
Indoor dew point
5.3 °C
20.0 °C · 38 % RH
Inner surface
19.1 °C
40 % RH at the inner surface
sd value
100 m
effective layers
Interstitial condensation
at 38 % indoors: outdoor temperature not down to −30 °C
at -5.0 °C outdoors: indoor humidity above 71 %
Surface mould risk
at 38 % indoors: outdoor temperature not down to −30 °C
at -5.0 °C outdoors: indoor humidity above 76 %

Cross-section

Temperature and dew point across the build-up – hover for details

Temperature Dew point (linear vapour pressure) Dew point above temperature Condensation (Glaser) Indoor air dew point
INSIDE20.0 °C · 38 %OUTSIDE-5.0 °C · 80 %131452319545286227ventilated – not effective-1001020°CwarmcoldDew point 5.3 °C
Values at layer boundaries
Boundaryx [mm]sd [m]θ [°C]θdew [°C]ps [Pa]p [Pa]RH [%]
Inner surface0.00.0019.15.32,21689240
1 | 213.00.1019.05.32,19189141
2 | 358.00.1514.55.31,65589154
3 | 458.210014.5-7.51,65532219
4 | 5253.2100-4.6-7.641532177
Outer side262.2100-4.7-7.641132178

Critical conditions

At which outdoor temperature and indoor humidity does it get critical?

safe Mould risk (surface > 80 %) Interstitial condensation current conditions
020406080100-30-20-1001020% RH insideOutdoor temperature in °C (inside 20.0 °C, outside 80 % RH)

Glaser diagram

Vapour pressure must not touch the saturation pressure

Saturation pressure Vapour pressure (Glaser)
1234505001,0001,5002,0002,500Painsideoutsidetotal sd 100 m

How it works

Temperature profile

The temperature drops across each layer in proportion to its thermal resistance R = d/λ. Surface resistances are Rsi = 0.25 and Rse = 0.04 m²K/W (0.08 behind a ventilation gap). Layers outside a ventilated air gap are ignored.

Dew point & condensation

The indoor air has a dew point (e.g. 9.3 °C at 20 °C / 50 %). Reaching it inside the build-up alone is not a problem – what matters is how much vapour gets there. The Glaser method compares the vapour pressure with the saturation pressure; where they meet, condensation forms.

Limitations

A steady-state estimate (EN ISO 13788) without capillary transport, moisture storage or thermal bridges. Capillary-active internal insulation is rated conservatively. For a detailed assessment use a hygrothermal simulation (e.g. WUFI).

endese