Template

Swedish 1970s house, insulated outside

Common retrofit (tilläggsisolering): a 1970s timber frame wall with an extra 70 mm of mineral wool and new wind barrier and panel outside.

  • Sweden
8 layers · 274 mm

Delete “Swedish 1970s house, insulated outside”?

This template will be removed for everyone. This can’t be undone.

Climate

20.0 °C
10 °C 28 °C
38 %
20 % 95 %
-5.0 °C
-30 °C 40 °C
80 %
30 % 100 %

Build-up

Layers from inside to outside

Inside (warm) 8 layers · 274 mm
  1. 1 Gypsum plasterboard
    mm
  2. 2 PE vapour barrier (sd 100 m)
    mm
  3. 3 Mineral wool 035
    mm
  4. 4 Old asphalt-impregnated board
    mm
  5. 5 Added insulation (tilläggsisolering)
    mm
  6. 6 Gypsum wind barrier board
    mm
  7. 7 Ventilation gap ventilated
    mm
  8. 8 New wood panel (träpanel) not effective
    mm
Outside (cold)

Result

No condensation

The indoor dew point (5.3 °C) is reached in layer 3 “Mineral wool 035” – but so little vapour gets there that the vapour pressure stays below saturation.

U-value
0.19 W/m²K
per EN ISO 6946
Indoor dew point
5.3 °C
20.0 °C · 38 % RH
Inner surface
18.8 °C
41 % RH at the inner surface
sd value
100 m
effective layers
Interstitial condensation
at 38 % indoors: outdoor temperature not down to −30 °C
at -5.0 °C outdoors: indoor humidity above 92 %
Surface mould risk
at 38 % indoors: outdoor temperature not down to −30 °C
at -5.0 °C outdoors: indoor humidity above 74 %

Cross-section

Temperature and dew point across the build-up – hover for details

Temperature Dew point (linear vapour pressure) Dew point above temperature Condensation (Glaser) Indoor air dew point
INSIDE20.0 °C · 38 %OUTSIDE-5.0 °C · 80 %131212031247056287228ventilated – not effective-1001020°CwarmcoldDew point 5.3 °C
Values at layer boundaries
Boundaryx [mm]sd [m]θ [°C]θdew [°C]ps [Pa]p [Pa]RH [%]
Inner surface0.00.0018.85.32,17589241
1 | 213.00.1018.65.32,14289142
2 | 313.210018.6-7.52,14232315
3 | 4133.21004.7-7.585632238
4 | 5145.21003.6-7.679232241
5 | 6215.2100-4.5-7.642032176
Outer side224.2100-4.6-7.641432178

Critical conditions

At which outdoor temperature and indoor humidity does it get critical?

safe Mould risk (surface > 80 %) Interstitial condensation current conditions
020406080100-30-20-1001020% RH insideOutdoor temperature in °C (inside 20.0 °C, outside 80 % RH)

Glaser diagram

Vapour pressure must not touch the saturation pressure

Saturation pressure Vapour pressure (Glaser)
12345605001,0001,5002,0002,500Painsideoutsidetotal sd 100 m

How it works

Temperature profile

The temperature drops across each layer in proportion to its thermal resistance R = d/λ. Surface resistances are Rsi = 0.25 and Rse = 0.04 m²K/W (0.08 behind a ventilation gap). Layers outside a ventilated air gap are ignored.

Dew point & condensation

The indoor air has a dew point (e.g. 9.3 °C at 20 °C / 50 %). Reaching it inside the build-up alone is not a problem – what matters is how much vapour gets there. The Glaser method compares the vapour pressure with the saturation pressure; where they meet, condensation forms.

Limitations

A steady-state estimate (EN ISO 13788) without capillary transport, moisture storage or thermal bridges. Capillary-active internal insulation is rated conservatively. For a detailed assessment use a hygrothermal simulation (e.g. WUFI).